Home › Guides › Wiring and electrical safety
Arc-fault breaker: where the Code requires it
Not just in bedrooms: since the 2018 Code, almost every outlet in the house. The exceptions, Québec’s own rules, renovations and tripping for no obvious reason.
In short
An arc-fault breaker shuts off the circuit when it detects an electrical arc, in the wiring or inside an appliance.
- Since the 2018 Code, it’s required on nearly every 120 V outlet in a dwelling, not just in bedrooms.
- Exceptions: kitchen counter outlets, bathroom outlets, the refrigerator outlet, and the single outlet for a sump pump.
- Québec adds its own rules, including a maximum of 10 outlets per protected circuit.
- Adding an outlet to an old circuit doesn’t mean redoing everything: an arc-fault outlet as the first outlet added is enough.
Jump to a section9
What it detects
If you read that an arc-fault breaker is only required in bedrooms, that was true before 2018. It isn’t anymore. Here is what the Québec Construction Code requires today, with the sections.
An electrical arc is current jumping through the air between two points, in the wiring or in an appliance. The arc-fault breaker is designed to recognize this kind of fault and cut the circuit.
The Code requires the combination type, which detects two kinds of arcs: series arcs and parallel arcs. The older type, which only saw parallel arcs, is no longer permitted in a new installation.
How it works
Not every arc is dangerous: opening a light switch or running a motor produces arcs normally. The arc-fault breaker constantly monitors the current and tells normal arcs apart from dangerous ones. According to a technical report by the U.S. Consumer Product Safety Commission, normal arcs repeat with every 60 Hz cycle, while dangerous arcs are irregular; the device looks at certain frequencies, discontinuities and irregularities in the current waveform.
A series arc happens when the current’s path is accidentally broken, in series with the appliance: a loose connection at an outlet or a splice, a wire worn from bending, a pinched cable. Its current is limited by the appliance plugged in: an ordinary breaker would never trip.
A parallel arc runs between two conductors of opposite polarity; it carries more energy and is generally considered more dangerous. The instantaneous trip of a 15 or 20 A residential breaker is usually set between 140 and 225 A, and ordinary fuses and breakers don’t respond to the first arcs and sparks.
The combination type protects against both kinds of arcs, over the whole branch circuit, including the cords of the appliances plugged in. According to the same report, an arc-fault breaker also usually has a 30 mA ground current sensor that picks up insulation breaking down before an arc. An arc-fault outlet, on the other hand, gives little protection to the wiring ahead of it, according to Ontario’s Electrical Safety Authority: that explains the protection required for the wiring between the breaker and that outlet.
Its limit: it reduces the effects of an arc without eliminating them, and the first arc can sometimes start a fire before the power is cut.
Where it’s required
In the 2026 Code, in force since March 26, 2026, the rule is Section 26-658. Work started before October 17, 2027 can still follow the 2018 Code, where the section has another number; the requirement to protect almost every outlet dates from the 2018 Code. In a dwelling, every branch circuit supplying 125 V outlets of 20 A or less must have combination-type arc-fault protection. The Corporation des maîtres électriciens du Québec (CMEQ) summed it up this way in 2019, at the time of the change:
“From now on, it will be everywhere there is a 120 V 15 A or 20 A outlet. Yes, you read that right, everywhere!” (translated from French)
CMEQ, Informel, January 2019
In practice, the CMEQ names, among others, the outlets in the living room and for the microwave, central vacuum, washer, dishwasher and attached garage. Outdoor outlets on the house become both GFCI and arc-fault protected. A lighting-only circuit isn’t covered.
Since when? The CMEQ says the 2018 Code is mandatory for work started after April 1, 2019. Before that, the requirement covered bedrooms.
The exceptions
In 2019, the CMEQ listed the outlets that don’t need arc-fault protection:
- kitchen counter outlets, including the island and the peninsula;
- bathroom outlets, if the branch circuit doesn’t supply other outlets;
- the refrigerator outlet;
- the single outlet for a sump pump.
Québec broadens this last exception: a single outlet for a sump pump, a sewage pump or an electro-medical device is exempt, if the outlet is permanently marked and the circuit supplies no other outlet. Outlets in a detached building (detached garage, shed) are also exempt, as are EV charging outlets.
Québec’s rules
Québec’s Code amends Section 26-658 on four points. Three are summarized here; the fourth, adding outlets to an existing circuit, is explained in the Renovations section.
| Québec rule | What it means |
|---|---|
| 10 outlets at most per arc-fault circuit | A protected circuit can’t supply more than 10 outlets. |
| Arc-fault outlet at the first outlet, instead of the breaker | Allowed, but the wiring between the breaker and that outlet must be in metal raceway or armoured cable. Non-metallic conduit, allowed elsewhere in Canada, isn’t allowed in Québec. |
| Broader exception | The single outlet for a sewage pump or an electro-medical device is added to the one for a sump pump. |
“the number of outlets that may be installed on a branch circuit with arc-fault protection must not exceed 10” (translated from French)
Québec Construction Code, Chapter V (Electricity), Section 26-658 4)
Renovations
| You’re doing… | What the Code asks |
|---|---|
| A new outlet branch circuit in an existing house | It must be arc-fault protected, as in new construction. |
| You’re adding outlets to an old circuit with no protection | An arc-fault outlet installed as the first outlet added is enough. No need to protect the whole existing circuit. |
| You’re replacing the panel without touching the circuits | The Code doesn’t require any change to existing circuits that aren’t touched. Your electrician tells you what applies in your case. |
A point of caution raised by the City of Winnipeg: a hardwired smoke or carbon monoxide alarm shouldn’t be on a circuit that is being modified, unless it has a backup battery. Mention it to your electrician. For how a replacement goes, see replacing an electrical panel: how it works.
Renovating, or replacing your panel?
We tell you what the edition of the Code in force requires in your home, and you get the price in writing before the work starts.
Send my quote requestWhen it trips for no obvious reason
The manufacturer Siemens names the causes to check:
- a neutral shared between two circuits;
- a neutral badly connected, at the breaker or on the appliance side;
- a neutral in contact with ground somewhere along the circuit;
- an overload, or a short circuit in an appliance;
- an actual arc, in the wiring or inside an appliance.
According to the City of Winnipeg, older non-combination models can be prone to nuisance tripping. Before calling, press the TEST button: it should trip. Then have the circuit checked. Replacing an arc-fault breaker with an ordinary breaker isn’t a solution: it removes a protection the Code has required on outlet circuits since the 2018 Code. For the full steps, see our guide breaker keeps tripping.
Arc-fault, GFCI or both
The two protections don’t do the same job. A GFCI cuts the power on a current leak to ground, to protect people. An arc-fault breaker cuts the power on an arc, to prevent fire. There are dual-function breakers that do both: Siemens, the panel brand we install most often, makes them.
| Outlet | Arc-fault | GFCI |
|---|---|---|
| Bedroom, living room, dining room | Yes | Depends on the location |
| Kitchen counter | No (exception) | See our GFCI guide |
| Bathroom | No (exception) | See our GFCI guide |
| Outside the house | Yes | Yes |
| Attached garage | Yes | Depends on the location |
| Detached garage, shed | No (exception) | Depends on the location |
| EV charger on an outlet | No (exception) | Depends on the outlet and the location |
To know where a GFCI is required, see our guide GFCI: what it protects, and where you need one.
Frequently asked questions
Is it only required in bedrooms?
No, not since the 2018 Code. In the 2026 Code, Section 26-658 covers every branch circuit supplying 125 V outlets of 20 A or less in a dwelling, except for the exceptions: kitchen counter, bathroom, refrigerator, single pump outlet.
Do I have to replace all my breakers if I replace my panel?
The Code doesn’t require any change to existing circuits that aren’t touched. On the other hand, every new outlet circuit must be protected. Your electrician tells you what applies in your case.
Why does my arc-fault breaker trip?
The manufacturer Siemens names, for instance, a shared neutral, a badly connected neutral or one in contact with ground, an overload, or an actual arc in the wiring or inside an appliance. Press TEST to check that it works, then have the circuit checked.
What’s the difference with a GFCI?
A GFCI cuts the power on a current leak to ground, to protect people. An arc-fault breaker cuts the power on an electrical arc, to prevent fire. A dual-function breaker does both.
How many outlets per arc-fault circuit?
In Québec, 10 outlets at most per arc-fault protected branch circuit. It’s a rule specific to Québec (Section 26-658 4)).
Since when has it been required everywhere?
Since the 2018 Code. According to the CMEQ, it’s mandatory for work started after April 1, 2019. Before that, the requirement covered bedrooms.
Can I install an arc-fault breaker myself?
No. The Régie du bâtiment du Québec says all work on an electrical installation, even at home, has to be carried out by a contractor who holds the appropriate licence. The manufacturer Siemens also states that its arc-fault breakers must be installed by a qualified electrician.
An arc-fault breaker that keeps tripping, or a renovation to plan?
We find the cause rather than removing the protection, and we explain what the Code requires in your home. Free quote.
4.9 from 549 Google reviews · RBQ licence 5815-0137-01 · CMEQ members · Free detailed quote
Get a quote: electrical panel
Sources
Consulted on October 4, 2026; the sources of the “How it works” section on October 28, 2026. The Code changes: check the edition in force before committing to any expense.
- LégisQuébec, Construction Code, Chapter V, Québec amendments (Section 26-658) (in French)
- CMEQ, Informel, January 2019 (arc-fault protection) (in French)
- CMEQ, 8 major Code changes (in French)
- RBQ, extension of the transition period, August 26, 2026 (in French)
- Siemens Canada, load centres and breakers catalogue
- Siemens, nuisance tripping of arc-fault breakers
- ESA (Ontario), bulletin 26-18-15, combination type (Canadian Code base rule)
- City of Winnipeg, bulletin 2026-002-E on arc-fault protection (hardwired alarms)
- RBQ, work homeowners can do themselves (in French)
- U.S. Consumer Product Safety Commission, New Technology for Preventing Residential Electrical Fires: Arc-Fault Circuit Interrupters
- U.S. Consumer Product Safety Commission, Preventing Home Fires: Arc Fault Circuit Interrupters, fact sheet 5133