Home generator maintenance
Exercise, oil, winter, warranty: what the manufacturers’ manuals ask for a standby or portable generator, and who handles what in Québec.
In short
A generator’s maintenance follows its manufacturer’s manual: the frequency and the points to check are written there.
- A standby generator runs its exercise on its own: 5 minutes every two weeks by default on Generac 10, 14 and 18 kW units, 15 minutes on the Champion 100515.
- In cold weather, Generac asks that the oil and filter of its 10 to 26 kW units be changed every year or every 100 hours (2023 manual).
- For its warranty, Generac requires proof of all required maintenance.
- The gas side belongs to a company that holds the appropriate licence from the Régie du bâtiment; we do the electrical side.
- A portable generator should be run for 30 minutes every 30 days, according to Generac’s GP series manual. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.
Jump to a section8
The automatic exercise
A standby generator starts on its own at a set interval; according to Kohler, this exercise keeps the engine and alternator in good operating condition. Its length and frequency vary from one brand to another.
| Brand and models | Automatic exercise |
|---|---|
| Generac, 10 to 26 kW (2023 manual) | About 5 minutes; weekly, every two weeks or monthly, as chosen |
| Kohler, 14, 20 and 26RCA (2023 manual) | 20 minutes, without load, once a week; the controller can also be set to every two weeks or monthly |
| Champion, model 100515 (2025 manual) | 15 minutes, fixed length; weekly at the most frequent setting |
On a Generac, the house is not transferred to the generator during the exercise, unless the grid goes down.
The exercise only runs if the generator is in AUTO mode, on a Generac as on the Champion 100515.
A Generac maintenance schedule
The brand we install most often is Generac. Here is the schedule from its 2023 manual, for the air-cooled 10 to 26 kW models.
| When | What |
|---|---|
| Before each use, or daily if running continuously | Enclosure louvers, fuel or oil leaks, oil level |
| After the first 25 hours | Oil and filter; valve clearance where applicable |
| Every year | Water intrusion; fuel system leak test |
| Schedule A: every two years or 200 hours | Oil and oil filter |
| Schedule B: every four years or 400 hours | Oil, oil filter, air filter, spark plugs, and valve clearance where applicable |
The controller itself displays the Schedule A or Schedule B alert.
The battery is inspected according to the manual’s schedule; the controller displays a warning when it needs service.
During a long outage, Generac asks that the oil level be checked daily: the generator shuts down if the level is low.
These intervals are those of this revision of the manual: the manual for your unit is the one that counts.
Kohler and Champion
At Kohler, according to its 2023 manual for the 14, 20 and 26RCA, the schedule depends on the model. On the 14 kW units, the oil is changed every year or every 100 hours, and the oil filter every year or every 200 hours.
On the 20 and 26 kW Kohler units, standard oil is changed every year or every 150 hours.
Kohler also asks that the battery charger be checked monthly, and that the terminals be cleaned and tightened every year.
On the Champion 100515, according to its 2025 manual, the oil and filter are changed after the first 5 hours, then every 2 years or every 100 hours, when the maintenance light comes on.
Champion’s manual also calls for a monthly check of the oil level, the fuel lines and fittings, and the battery terminals.
Winter
Cold shortens the oil interval of a Generac 10 to 26 kW unit (2023 manual): below 4.4 °C, the oil and filter are changed every year or every 100 hours.
The same Generac manual recommends a cold weather kit where temperatures fall below 0 °C. Below -18 °C, it also recommends a battery warmer and an oil heater, sold separately.
For its 14, 20 and 26RCA, Kohler for its part recommends heater kits where the temperature drops below 0 °C.
Warranty and maintenance
The warranty is the manufacturer’s. At Generac, it lasts 5 years or 2,000 hours, whichever comes first.
Generac requires that proof of all required maintenance be available. The costs of normal maintenance are not covered, nor is the starting battery.
Who does the maintenance? Generac recommends an authorized service dealer; what its warranty reserves for the dealer is warranty repairs.
Kohler asks that an authorized dealer service the generator at the scheduled intervals, and that the owner keep the maintenance records.
Champion requires scheduled maintenance; its warranty allows it to be done by an experienced and competent operator or by an authorized dealer, with proof.
Either way, keep the invoices and log each service: Generac’s manual includes a maintenance log for that.
Gas and electricity: who handles what
A standby generator has two sides. The gas side, propane or natural gas, belongs to a gas company that holds the appropriate licence from the Régie du bâtiment. We do the electrical side.
The Régie confirms it: construction work in the gas field requires the appropriate licence.
Generac advises performing the fuel system leak test during scheduled maintenance.
After a flood, Generac asks not to start a generator that has been submerged and to have it inspected by its service dealer.
On the electrical side, we connect the generator, we run a complete transfer test, and we show you what to look at and what the manufacturer’s manual says about maintenance.
A generator to connect?
Tell us what you want to keep running during an outage, and you get the price in writing.
Send my quote requestPortable generators
A portable generator has its own schedule. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.
Here is what Generac’s manual asks for its GP series (GP6500 and GP8000E, 2020 revision):
- the oil level, at each use;
- the oil, changed after the first 30 hours, then every 100 hours;
- the air filter, inspected and cleaned every 200 hours, more often in dusty conditions;
- the spark plug and the valve clearance, every year.
Generac recommends running it for 30 minutes every 30 days. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.
Fuel is the weak point: stored more than 30 days, it can degrade and damage the fuel system. The manual offers two ways to store the unit: drain the fuel system, or stabilize the fuel, which then keeps for 24 months at most.
Before storing it, Generac asks that the oil be changed, that the unit cool down before being covered, and that it be kept in a clean, dry place, with the generator and fuel away from sources of heat and ignition.
To connect it to the house, you need a power inlet and a transfer switch: it is explained in our generator transfer switch guide. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.
Frequently asked questions
How often does a generator run its exercise?
It depends on the brand. A Generac 10, 14 or 18 kW unit runs for 5 minutes every two weeks by default; Kohler asks for 20 minutes a week for its 14, 20 and 26RCA; the Champion 100515 runs for 15 minutes.
When should the oil of a Generac generator be changed?
After the first 25 hours, then every two years or 200 hours. In cold weather, below 4.4 °C, Generac asks for every year or every 100 hours (2023 manual, 10 to 26 kW models).
Is maintenance required for the warranty?
At Generac, yes: proof of all required maintenance must be available. Champion also requires scheduled maintenance. Keep the invoices.
Who handles a generator’s gas side?
A gas company that holds the appropriate licence from the Régie du bâtiment. We do the electrical side.
Is a cold weather kit needed in Québec?
Generac recommends it for its 10 to 26 kW units (2023 manual) where temperatures fall below 0 °C, and Kohler recommends heater kits for its 14, 20 and 26RCA in the same conditions.
How do you maintain a portable generator?
According to Generac’s GP series manual: oil every 100 hours, air filter every 200 hours, and 30 minutes of running every 30 days. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.
A generator to connect?
We connect the generator to the panel, run the transfer test and show you how to use it.
4.9 from 580 Google reviews · RBQ licence 5815-0137-01 · CMEQ members · Free detailed quote
Get a quote: generator
Sources
Read on November 16, 2026; each interval applies to the model and manual revision cited.
- Generac, owner’s manual for 10 to 26 kW generators, 2023 revision (PDF)
- Generac, 10, 14 and 18 kW spec sheet (PDF)
- Generac, 5-year limited warranty (PDF)
- Kohler, operation manual for the 14, 20 and 26RCA, September 2023 revision (PDF)
- Champion, operator’s manual for model 100515, April 2025 revision (PDF, in French)
- Generac, GP series owner’s manual, 2020 revision (PDF)
- Régie du bâtiment du Québec, licence in the gas field (in French)
- Health Canada, preventing carbon monoxide exposure (in French)
CAA Habitation recommended