Automatic transfer switch for a home generator

It senses the outage, starts the generator and switches the house over without you stepping outside. Here is how, and which one is allowed in Canada.

Get a quote

By the master electricians of STM-ÉlectriqueRBQ licence 5815-0137-01Sources checked on November 22, 2026

In short

An automatic transfer switch senses the outage, starts the generator, hands the house over to it within seconds, then returns to the grid on its own.

  • Generac’s factory settings: start 10 seconds after the grid is lost, 5 seconds of warm-up, return to the grid 15 seconds after it is restored.
  • In Canada, you need a listed model: Generac states that the 200 A switch in its bundles is certified for the US only.
  • Generac offers cETLus models of 100, 200 and 400 A; Kohler, an RXT that is CSA-certified in 100 and 200 A.
  • It can supply the whole house or only the essential circuits.
Jump to a section7
  1. How it switches
  2. Listed for Canada
  3. At the service entrance or after
  4. Whole house or essentials
  5. Manual or automatic
  6. Hydro-Québec and the CMEQ
  7. Frequently asked questions

How it switches, in four steps

Kohler sums up the sequence: the switch monitors the grid, detects the outage within seconds, the generator takes over the house, then the switch puts it back on the grid when power returns.

At Generac, the generator’s controller handles the sensing, the delays, the exercise and the transfer commands.

Generac’s factory settings, as its Canadian transfer switch sheet gives them:

StepFactory delay (Generac)
Before starting the generator10 s, adjustable from 2 to 1,500 s
Engine warm-up5 s
Before returning to the grid15 s
Engine cool-down60 s

According to Generac, the delay before starting prevents needless start-ups for a very short outage.

The switch drops the grid when voltage falls below 75 to 80% of normal, and returns when it climbs back to 84 to 89% (Power Zone controllers).

According to Generac, the switch can be operated manually with no power applied.

Listed for Canada

A common trap: on its 22 to 28 kW sheet, Generac writes that the 200 A “service entrance” switch in its bundles is certified for the US only.

For Canada, Generac has its series of listed automatic transfer switches: G0099490 at 100 A, G0099500 at 200 A and G0099380 at 400 A, 120/240 V, open transition, NEMA 3R outdoor enclosure, cETLus compliance.

At Kohler, the RXT comes in a CSA-certified “service entrance” version, offered in 100 and 200 A only.

Generac’s Canadian automatic transfer switches work with Generac generators that use an Evolution or Power Zone controller, the RXT with Kohler generators that use an RDC2 or DC2 controller.

The CMEQ points out that a distribution panel is not a transfer switch: you need a device approved for that use.

Everything we install carries Canadian certification.

At the service entrance or after the panel

A “service entrance” switch goes at the service entrance and backs up the whole house: its breaker serves as the main disconnect.

The RBQ specifies that a transfer switch placed at the service must be approved as service equipment.

Generac’s G0099500 is approved to serve as the service entrance disconnect in Canada, thanks to its built-in breaker.

Whole house or essentials

Kohler writes it in the RXT manual: you can supply the whole house or only the essential loads, as long as the generator and switch are rated for the loads chosen.

With load management, a smaller generator can be enough: Kohler manages up to six loads, and Generac’s “Load Managers” shed large loads during an overload.

What each generator size delivers is compared in our guide to the 18, 22, 24 or 26 kW generator.

Manual or automatic

The automatic switch goes with a standby generator, which starts on its own; the manual one, with a portable you start yourself and plug into an outdoor inlet.

For a portable, the safety rule applies. Never run it in the garage: place it at least 6 metres from buildings, as Health Canada recommends.

The manual switch is explained in our generator transfer switch guide.

What Hydro-Québec and the CMEQ require

According to the CMEQ, a transfer switch is always required to connect a generator to the home’s service, manual or automatic.

Hydro-Québec accepts a standby generator connected through switching equipment with a mechanical interlock that makes coupling with the grid impossible.

Without a mechanical interlock, or with closed transition, you need Hydro-Québec’s written authorization before connecting.

Generac’s Canadian switches are open transition.

Frequently asked questions

How long without power before the generator takes over?

With Generac’s factory settings: 10 seconds before starting, then 5 seconds of warm-up. The first delay is adjustable.

Can a switch bought in the US be installed here?

Not the 200 A switch in Generac bundles, certified for the US only. In Canada, you need a listed model, for example the G0099500 at Generac or the CSA-certified RXT at Kohler.

Do I need a 200 A switch?

Not always: it can back up the whole house or only the essential circuits, depending on the generator and the loads chosen.

Is a transfer switch required?

Yes: according to the CMEQ, a generator connected to the home’s service always needs a transfer switch.

Does a Generac switch work with a Kohler?

No: Generac’s Canadian automatic transfer switches work with Generac generators that use an Evolution or Power Zone controller, and the RXT with Kohler generators that use an RDC2 or DC2 controller.

An automatic transfer switch to install?

A model listed for Canada, the choice of backed-up circuits and the connection, with a written price before the work starts.