Home › Guides › Generators
18, 22, 24 or 26 kW generator
What each size really delivers, in kW and in amps, on propane and natural gas, based on Generac’s and Kohler’s spec sheets.
In short
On propane, Generac and Kohler generators from 18 to 26 kW deliver 75 to 109 A at 240 V, depending on size and brand; a 200 amp home can ask for more when everything runs at once.
- Generac’s 18 kW gives 75 A on propane and 71 A on natural gas.
- Generac’s 22 and 24 kW give 92 and 100 A on propane.
- At 26 kW, it is 108 A from Generac and 109 A from Kohler, on propane.
- A Generac 24 kW on propane delivers about half of what 200 amp service can let through: you pick the backed-up circuits or manage the loads.
Jump to a section6
What the kW means
The number in the name is the output on propane. On natural gas, the same generator gives a little less: 22.5 kW for a Generac 24 kW, 24 kW for a Kohler 26 kW.
These are maximums: Generac writes that they vary with the fuel, temperature, humidity and altitude.
To compare a generator with an electrical panel, amps at 240 V say more than kW: it is the unit of the main breaker.
Size by size
Figures from Generac’s sheets (August 2026 revisions) and Kohler’s (July 2023), single-phase 120/240 V:
| Size | Model | Propane | Natural gas | Amps at 240 V, propane / natural gas |
|---|---|---|---|---|
| 18 kW | Generac 18 kW | 18 kW | 17 kW | 75 / 71 |
| 20 kW | Kohler 20RCA | 20 kW | 18 kW | 84 / 75 |
| 22 kW | Generac 22 kW | 22 kW | 21 kW | 92 / 88 |
| 24 kW | Generac 24 kW | 24 kW | 22.5 kW | 100 / 94 |
| 26 kW | Generac 26 kW | 26 kW | 24 kW | 108 / 100 |
| 26 kW | Kohler 26RCA | 26 kW | 24 kW | 109 / 100 |
Above that, Generac makes a 28 kW: 116 A on propane, 104 A on natural gas.
The generator’s own breaker follows its size: 80 A for Generac’s 18 kW, 100 A for the 22 and 24 kW, 110 A for the 26 kW; 125 A for Kohler’s 26 kW.
Between a Generac 22 and 24 kW, the gap is 8 A on propane, with the same 100 A breaker.
Against 200 amp service
200 amp service is what the main breaker lets through before it trips.
A Generac 24 kW on propane delivers at most 100 A, and a Kohler 26 kW, 109 A: about half of 200 A.
A 200 amp home does not run everything at once; but if the heating, water heater, range and dryer all start together during an outage, the generator can run short of amps.
Hence two approaches: back up only certain circuits, or let a load management system decide.
Pick circuits or manage loads
Kohler says so in its transfer switch manual: you can supply the whole house or only the essential loads, as long as the generator and switch are rated for the loads chosen.
Kohler’s load management handles up to six loads, including two heating or air conditioning units; according to Kohler, it allows a smaller generator than running everything at once would need.
At Generac, 50 and 100 A “Load Managers” start large loads at the right time and shed them during an overload; Generac writes that they often reduce the size and cost of the system.
Generac also offers a thermostat that manages heating and cooling during the outage, and a contact that locks out a single large load you can do without.
The list of circuits to back up is explained in our generator transfer switch guide, and our generator size calculator adds up your appliances.
What manufacturers say
Kohler describes its sizes this way: the 14 kW powers “the basics, plus” the water heater, heating and air conditioning; the 20 kW, most major appliances; the 26 kW, the entire home; and a 48 kW, everything, with 200 amp service.
Generac presents its 28 kW as the standard for whole-home backup power.
These are manufacturer phrases. Kohler adds that the right size depends on square footage, the appliances to power and the installation.
Frequently asked questions
Will a 24 kW power a whole 200 amp house?
Not everything at once: on propane, a Generac 24 kW delivers at most 100 A, about half of 200 A. You pick the circuits or manage the loads.
Why fewer kW on natural gas?
That is what the sheets show: a Generac 24 kW gives 22.5 kW on natural gas, a Kohler 26 kW gives 24.
What is load management?
A system that starts large loads at the right time and cuts some when the generator nears its limit; Generac and Kohler say it allows a smaller generator.
22 or 24 kW?
At Generac, the 22 kW gives 92 A and the 24 kW 100 A on propane, with the same 100 A breaker; the choice depends on the loads to back up.
Is an 18 kW enough?
At Generac, it delivers 75 A on propane; in a 200 amp home, that is not enough to run everything at once, so you pick the backed-up circuits.
Not sure what size you need?
We assess the circuits to back up with you, and the price is written before the work starts.
4.9 from 580 Google reviews · RBQ licence 5815-0137-01 · CMEQ members · Free detailed quote
Get a quote: generator
Sources
Consulted on November 22, 2026. Each figure applies to the sheet named.
- Generac, 22 to 28 kW air-cooled standby spec sheet, A0005151077 Rev. D, August 13, 2026 (PDF)
- Generac, 10, 14 and 18 kW air-cooled standby spec sheet, A0005151081 Rev. D, August 13, 2026 (PDF)
- Kohler, 20RCA(L) spec sheet, G4-272, July 2023 (PDF)
- Kohler, 26RCA(L) spec sheet, G4-315, July 2023 (PDF)